Kruse (1991) recommends,
...select an economizer system which doesn't compromise the chiller efficiency by running dirty tower water through the chilled water side of the system. As other articles have pointed out, strainer cycles have not solved this problem and shell-and-tube heat exchangers are not effective enough due to large approach temperature requirements. A plate-[and-]frame heat exchanger design will usually offer the best choice.